On 8/23/14 we made some major structural changes to the website. Most links should be working and we are monitoring 404 errors. If something seems broken, please send us a note. Thanks for your patience.

Receive our newsletter

Sprinkler Head Spacing and Location

***WARNING: Fire suppression systems, including sprinklers, MUST be designed by a Professional Engineer. The information contained in this article is general in nature and is to be used as a GUIDELINE for architects. You must have a Professional Engineer design a sprinkler system to address your specific situation and to meet the codes applicable in your jurisdiction. The information in the article is based on NFPA 13.

Sprinkler Head Location

There are two main criteria for the location of sprinkler heads. First, sprinklers must be located so they are within the hot-gas layer that develops near the ceiling during a fire because activation occurs when the sprinkler head reaches a certain temperature. Second, they must be located so that the water that is discharged from the sprinkler is not disrupted or affected by construction elements such as beams, trusses, or soffits.

Water distribution for standard pendant sprinkler

The diagram at left shows the water distribution for standard pendant and upright sprinkler fixtures. It is useful to understand how objects within this distribution area can alter the throw and disrupt the ability of the sprinkler to extinguish a fire.


This is a general depiction of sprinkler throw and should not be used to determine sprinkler spacing. Refer to the manufacturer data for specific throw data. Please note, that the throw of a sprinkler should not be used for sprinkler spacing - local codes determine spacing requirements.





Sprinkler Head Spacing

The table below shows sprinkler spacing requirements based on NFPA 13. This table shall be used only as a tool for architects. Actual design of a sprinkler system MUST be done by a Professional Engineer for each project.

Occupancy Hazard Square Foot per Head Maximum Spacing Between Sprinklers
Light Hazard
(Office, Educational, Religious, Institutional, Hospitals, Restaurants, Clubs, Theaters, etc.)
130-200 SF per head
(based on obstructions and flow calcs)
15 ft
Ordinary Hazard
(Mills, Manufacturing, Processing, Machine Shops, Repair Garages, Post Offices, Bakeries, Wood Machining and Assembly, Auto Parking, etc.)
130 SF per head 15 ft
Extra Hazard
(Plastic Processing, Chemical Spraying, Metal Extruding, Printing, Varnishing, Painting, etc.)
90-130 SF per head
(based on obstructions and flow calcs)
12 ft

Maximum Distance from Wall: half (1/2) of the maximum distance between sprinkler heads.

Minimum Distance Between Sprinklers: typically 6'-0".

Distance from Ceiling: minimum 1", maximum 12" for unobstructed construction. The minimum 1" is typical; however, concealed, recessed, and flush sprinklers may be mounted less than 1" from the ceiling and shall be installed based on their listing.

Extended Coverage Sprinkler Heads

In some circumstances, standard distribution sprinkler heads will not provide enough coverage. In these cases, extended coverage sprinkler heads can be installed to increase the spacing between heads. Extended coverage sprinklers have a water distribution radius of a little over 10 feet, so they can be spaced approximately 20 feet apart.

2004 CSI Masterspec Division

Fire-Suppression Sprinkler Systems: 21 13 00


 


Help make archtoolbox better. If you found an error or out of date information in this article, please let us know.


   

Related Archtoolbox Articles